MIL-PRF-24236D
4.6.18 Overload cycling (see 3.23). Each switch shall be tested for overload cycling using the same voltage,
electrical frequency, and the same pair(s) of contacts that will subsequently be used for the electrical endurance test.
The switches shall close and open the overload current of a resistive circuit equal to 150 percent of the resistive load
rating and the particular voltage and electrical frequency. The cycling rate shall be less than 6 cycles of operation per
minute. Fifty cycles of operation shall be performed. The duty cycle shall be approximately 50 percent on, 50 percent
off.
4.6.19 Endurance (see 3.24). Switches shall be subjected to the specified number of cycles of make-and-break
4.6.20 Salt spray (corrosion) (see 3.25). Switches and their mounting hardware and brackets (if applicable) shall
be tested in accordance with method 101 of MIL-STD-202. The following details shall apply:
(a)
Applicable salt solution - 5 percent.
(b)
Test condition - B.
(c)
Measurements after exposure - Following the drying period, the switches shall meet the requirements
specified in 3.25. Mounting hardware shall be removed at the end of the test.
4.6.21 Sand and dust (see 3.26) (when specified, see 3.1 and 6.2.2). Switches shall be tested in accordance with
method 110 of MIL-STD-202. This test shall be performed with the pressure port suitably capped or plugged. The
following details shall apply:
(a)
Test condition - B.
Measurements - Switches shall be tested in accordance with 4.6.3.
(b)
4.6.22 Explosion (see 3.27) (when specified, see 3.1 and 6.2.2). Switches shall be tested in accordance with
method 109 of MIL-STD-202. The following detail shall apply:
(a)
Mechanical and electrical load - Switches shall be operated at their maximum rated dc inductive current
4.6.23 Low level (see 3.30) (when specified, see 3.1). Switches shall be tested for the number of cycles specified
(see 3.1) as follows:
(a)
Contact load - Each switch contact shall make, carry, and break a resistive load of 10 milliamperes
maximum at an open circuit voltage of 30 millivolts maximum dc or peak ac. Both normally open and
normally closed contacts shall be loaded. Contacts shall be connected to individual loads.
(b)
Operate cycles - Rate not to exceed 6 cycles per minute.
(c)
Monitoring circuit - The monitoring equipment shall provide a record of the number of cycles and shall
record failures, or discontinue the test, if a failure occurs. During each closure, the contact potential shall be
monitored for at least 50 percent of the time the contacts are closed.
4.6.24 Minimum current (intermediate current) (see 3.31) (when specified, see 3.1). Switches shall be subjected
to the number of cycles of make-and-break operations specified (see 3.1), in a circuit having a 27 +3 and -0 volt dc
source and a load consisting of the coil of relay, part number M5757/10-033, or equivalent. The cycling rate shall not
exceed 6 cycles per minute, and switches shall be monitored for make-and-break operations.
MIL-STD-202. The following details and exception shall apply:
(a) Portion to be brushed - All marking areas.
(b) Number of specimen to be tested - Three.
(c) Extent of mechanical or electrical damage - Not applicable.
19
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business