MIL-PRF-22710H
4.5.22 Life (rotational) (see 3.25). Switches shall be tested in accordance with 4.5.22.1, and when applicable (see
4.5.22.1 At atmospheric pressure. Switches shall be tested in accordance with method 206 of MIL-STD-202. An
actuating mechanism shall be used that basically duplicates the function of the mechanism described in method 206
for the switches. The following details and exception shall apply:
a. Test potential and load: Each switch section shall be energized by the specified test loads (see 3.1), with
each load applied to approximately the same number of sections. The first and last section shall be
energized with the resistive load of the highest voltage rating. The specified load for each section shall be
wired to the contacts which are subject to making or breaking the circuit during rotation of the switch shaft as
follows:
(1) Nonshorting type section: All contacts.
(2) Shorting type section: Alternate contacts only. The first and last section shall be energized with the
resistive load of the highest voltage rating. The specified load for each section shall be wired to each
contact of the section, which is subject to making or breaking during rotation of the switch shaft. Where
there are insufficient switch sections to accommodate all rated loads, the loads shall be apportioned,
approximately equally, among the other switches being subjected to the life (rotational) test.
b. Cycling and cycle rate: Manually actuated switches shall be cycled at the rate of 10 cycles per minute. At the
option of the contractor, cycling may be interrupted, periodically, after each 5,000 cycles of operation. Each
shaft of concentric shaft switches shall be rotated the total number of cycles prescribed.
c. Test-condition letter: As specified (see 3.1).
d. Operate cycle: The monitoring apparatus shall record the number of operating cycles. The test switches
should be manually operated, and contact resistance readings taken, at the beginning of the test and
immediately following the conclusion of each of the environments listed below, and changes in contact
resistance exceeding the maximum specified shall be noted. Unless otherwise specified (see 3.1), the test
shall be conducted in the following sequences and environments:
(1) 25 percent of the test cycles at room ambient temperature.
(2) 25 percent of the test cycles at maximum rated temperature.
(3) A 2-hour noncycling period at minimum rated temperature.
(4) 25 percent of the test cycles at minimum rated temperature.
(5) 25 percent of the test cycles at room ambient temperature.
4.5.22.2 At reduced barometric pressure. Switches designed for operation above 10,000 feet shall be tested as
specified in 4.5.22.1, and in accordance with method 105 of MIL-STD-202, except that the temperature condition
shall be room ambient. The following details shall apply:
a. Method of mounting: On a vertical corrosion-resistant panel.
b. Test-condition letter: C or D, as applicable (see 3.1).
c. Tests during subjection to reduced pressure: Switches shall be operated at the applicable test loads (see
3.1).
After the test, switches shall be examined for broken, deformed, displaced, or loose parts.
24
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business